Check manual page of wagner_titanus_topsense.alarm
Wagner Titanus Top Sens: Alarms Triggered
Distribution: | official part of Check_MK |
License: | GPL |
Supported Agents: | SNMP |
Checks if alarms have been triggered on an Wagner Titanus Top Sens device.
If pswMainAlarm is triggered, the check returns CRIT, if pswPreAlarm or
pswInfAlarm is triggered, it return WARN and if none of these is triggered
it returns OK.
Item
The ID of the detector.
Discovery
Creates two checks on every Top Sense device, one for each detector.